Data Center Battery Fires: What Fire Chiefs Should Plan For

By Joel Yonkman

On the evening of September 26, 2025, technicians at South Korea's National Information Resources Service in Daejeon disconnected a lithium-ion battery module from an uninterruptible power supply (UPS) so it could be moved during maintenance. One cell failed and thermal runaway spread across the rack. The fire burned for almost 22 hours, destroyed 384 battery modules and forced 647 government systems offline, roughly a third of the country's online public services. More than 200 firefighters and over 60 vehicles responded (ESS News, Sept. 30, 2025).

Three years earlier, a fire involving backup-power batteries at an SK C&C data center in Pangyo took down Kakao's messaging, payment and taxi services for days (Bloomberg via Data Center Knowledge, Oct. 24, 2022).

Neither event started in a server hall. Both started in the battery systems that keep the servers running. In our work with host communities, that is the part of a data center fire chiefs most often know the least about when the site plan arrives. This article sets out what a department should plan for, and what to settle with the developer before the building goes up.

Why are data center batteries a fire service problem?

Every data center carries stored energy to ride through a utility outage until the generators start. Lithium-ion has become a common choice for that UPS role because it is compact and long-lived. The trade-off is thermal runaway: a failing cell heats its neighbors, releases flammable and toxic gases, and can reignite after it appears to be out.

For a fire department, that changes four things:

  • Duration. A battery fire may not end when visible flame does. The Daejeon fire ran close to a full day.

  • Gas, not just smoke. Vent gases can accumulate in a closed battery room and create a deflagration hazard before crews make entry.

  • Water and power. Crews need to know what can be de-energized, who can do it, and how long the stored energy remains live after it is isolated.

  • Consequence. The hazard is small in footprint but large in effect. A single room can take down services an entire region depends on, as both Korean incidents showed.

What do the codes require for battery systems?

Two documents carry most of the weight in the United States.

The International Fire Code, Section 1207. As adopted in Washington State, for example, the section applies to lithium-ion systems above a 20 kWh threshold and requires a failure modes and effects analysis or other approved hazard mitigation analysis in defined conditions, large-scale fire testing in accordance with UL 9540A to show that a fire in one unit will not spread to an adjacent unit, explosion control for lithium-ion installations, and a fire safety and evacuation plan (WAC 51-54A-1207). A data center's UPS banks are measured in hundreds or thousands of kilowatt-hours, so they sit far above that threshold.

NFPA 855, 2026 edition. The new edition makes the hazard mitigation analysis the default expectation for most energy storage installations rather than a requirement triggered only when a project exceeds prescriptive limits. It adds minimum requirements for an emergency response plan that addresses mitigation, preparedness, response and recovery, with an annual review and annual refresher training, and notification of the authority having jurisdiction. It also requires large-scale fire testing alongside UL 9540A (Energy-Storage.news, Feb. 2026).

Which edition applies depends on what your state and jurisdiction have adopted. The point for a fire chief is that the codes now expect the owner to analyze the hazard and to plan the response with the fire service. That gives the department a place at the table, but only if it asks for it before the permit is issued.

What should a fire chief ask for before a data center is approved?

The questions below are the ones we see settled too late. Each is easier to secure as a condition of approval or a term of the development agreement than after construction starts.

Battery inventory and location

Ask for the chemistry, total energy in kilowatt-hours, number and location of battery rooms, and the UPS manufacturer and model. Ask whether any outdoor battery energy storage is planned for grid services or on-site generation, which is a different hazard from the indoor UPS.

The hazard mitigation analysis and test data

Request the hazard mitigation analysis and the UL 9540A and large-scale fire test reports for the specific systems proposed. These documents tell the department what a failure is expected to look like, what gases are produced and whether a fire is expected to stay in one unit.

Detection, suppression and explosion control

Confirm off-gas detection in battery rooms, how detection is annunciated to the fire alarm system, the suppression approach, and the explosion control design. Ask how the system behaves if a crew opens the door during an event.

Emergency response plan and a named contact

Require the owner's emergency response plan before occupancy, with a 24-hour subject-matter expert who can reach the incident commander quickly and who knows how to isolate and monitor the system. The plan should cover how long crews should expect to stay on scene and who manages a damaged battery after the fire.

Pre-incident plan, access and water

Build the pre-incident plan with the owner: battery room locations, shutoffs, access routes inside a secured campus, staging, water supply and runoff. Data center campuses are large and security-controlled. Gate codes and escort arrangements belong in the plan, not in a phone call during the incident.

Training and exercises

Ask for site familiarization for every shift, joint training with the owner's facility staff and a tabletop exercise on a battery room event before the building opens. NFPA 855's annual review and refresher cycle is a natural hook for repeating that each year.

Who should pay for the planning work?

The planning, pre-incident work, training and exercises described above take staff time a local department rarely has. In our experience the best time to address cost is at the very start, in the pre-application meeting, the conditions of approval or the development agreement. Written in early, much of that work can be funded by the developer rather than the county or the fire district. It cannot be guaranteed in every case, but it is rarely available once approvals are final.

Frequently asked questions

Do data centers use lithium-ion batteries?

Many do. Lithium-ion is a common choice for UPS systems because of its size and service life. Both Korean incidents described above involved lithium-ion batteries in backup power systems.

Can a fire department put out a lithium-ion battery fire with water?

Water is used to cool batteries and limit spread, but a battery in thermal runaway can reignite after flames are knocked down. In Daejeon, crews moved from carbon dioxide and limited spraying to immersion and cooling methods. Tactics should come from the owner's emergency response plan, the test data and the department's own procedures.

What is UL 9540A?

UL 9540A is a test method that evaluates thermal runaway propagation at the cell, module, unit and installation levels. Codes use its results, and large-scale fire testing, to judge whether a fire in one unit will spread to the next.

When should the fire service get involved in a data center project?

At pre-application. Conditions of approval and development agreements are the strongest tools a jurisdiction has, and both are settled before the building permit.

Planning before the site plan

Data centers bring real benefits to the communities that host them. They also bring a hazard most departments have not trained on. The work is manageable when the questions are asked early, the owner shares the data and the fire service has a plan in hand before opening day.

ERGSS supports county emergency managers, fire chiefs and data center owners with critical infrastructure planning, pre-incident planning, training and exercises. To talk through a project in your jurisdiction, contact us at info@ergss.com or (202) 978-2666.

Joel Yonkman is the founder of ERGSS (Emergency Response & Global Security Solutions). He is a paramedic and emergency manager who served as Planning Section Chief on FEMA Region VI's Incident Management Assistance Team and worked major responses including Deepwater Horizon. More at joelyonkman.com.